Cold Roof Constructions - Duo-pitched roofs 15° pitch or less

All duo-pitched roofs 15° pitch or less with a high resistance underlay installed. Insulation at ceiling level.

Quick Links

Decra Eaves Ventilation System
Which is the right eaves ventilation system for your roofing project? Read more 

Ridge Ventilation Components
Which is the right ridge ventilation system for your roofing project?
Read more

Tile Ventilation Components
Read more about the range of tile ventilation components and their order codes

Tile Ventilator Spacing Charts
Reccommended tile ventilation spacings to acheive 5,000mm², 10,000mm² or 25,000mm² per linear metre please click on the appropriate link below
Decra Classic and Elegance
Decra Stratos and Oberon
Parctile

Requirements:

Eaves ventilation equivalent to 25mm continuous opening (on opposite pitches), and ridge ventilation with a continuous opening equal to 5mm at each side of ridge.

Decra Solution:

i) DecraVent 25mm Eaves Packs, each pack providing ventilation for 6 metres of eaves, installed to provide continuous ventilation to both eaves.

Alternatively: Tile vents at appropriate centres to provide equivalent of a 25mm continuous opening.

ii) Decra Universal Ridge/Hip Ventilator (all Decra tile profiles) or DecraVent D Ridge system (Decra Classic, Elegance, Parctile, only) providing continuous ridge ventilation.

Alternatively: Tile vents at appropriate centres to provide equivalent of a 5mm continuous opening.